ONECALLPOINT

Addressable Manual call point

Functional Features
Activation is signaled with a red led and glass break effect, the call point can be reset with the provided key. Each call point is provided with an integrated short circuit isolator that automatically takes action in case of need. The address can be programmed by means of the programmer or with the addressing function of Teledata smoke detection panels. It is provided with tools for base numbering and locking pins against unwanted removal.

Technical Features
• Provided with integrated isolator circuit
• Red color led
• Flush-mounted installation tool included
• Power supply: 18-35V
• Average current consumption: 120 μA
• LED current consumption: 6mA (24V- line)
• Operating temperature: –20°C + 65°C
• Max. humidity: 95%
• Dimension: 87x87x54 mm
• Max. Cable cross-section 2.5 mm²

Brand

Teledata